AUX EL Series Instrukcje Operacyjne Strona 9

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 8
09/11/2014 7 NI401
Figure 1
Horizontal Closed Loop
Mechanical Installation Overview
This NorthStar Series unit cannot correct airflow problems inherent within the duct work system. The following
items should be carefully considered and properly followed for all installations:
Examination of the existing forced air furnace Prior to starting this installation, examine the total furnace
system and make necessary comments or recommendations to the homeowner. Remember, if a marginal
condition exists within the existing duct work system, the installation of a geothermal heat pump will not cure
PRE-EXISTING conditions. Consider such items as adequate cold air return and adequate supply duct and
room register (1 register per 100 CFM) etc.
Heating capacity Size the geothermal heat pump according to the normal heating requirements as the
building exists today. Do not necessarily match to the existing furnace nameplate because it may be oversized.
Do not oversize the geothermal heat pump.
Other plenum equipment Auxiliary equipment such as humidifiers, zone plenum dampers, etc., located
within the plenum which may cause a non-uniform airflow issues may have to be removed if they cause
excessive reduction to system airflow. Zone dampers within the trunk line at least 12" (30.5 cm) from the coil
typically pose no problems. When horizontal zone dampers are involved, perform all check-out functions with
smallest zone open first.
Comment zone dampers cause back pressure on the blower and overall reduced airflow. Reduced
airflow can cause the geothermal unit to perform poorly or in some cases cause icing or freeze ups in
the geo loop or air coil.
Insufficient cold air return capacity Installation experience indicates this is a major concern. In fact, it
could represent a problem in as many as 60% of the installations, especially if there is a requirement to increase
airflow when the existing cold air return capacity is already undersized or restricted. Check the static pressure
within the return cabinet or the suction at the filter cabinet door. Do not assume because there is a register on
the wall, the hole behind the register or the passageways are equal to this register. Sharp offsets and transitions
in the cold air return system often cause severe restrictions. Expect to add additional registers or a relief register
in the main cold air return duct.
Closed Loop Applications Closed loop system re-circulates the same water/antifreeze solution through a
closed system of underground high-density polyethylene pipe. As the solution passes
through the pipe it collects heat (in the heating mode) that is being transferred
from the relatively warm surrounding soil through the pipe and into the
relatively cold solution. The solution is circulated back to the heat pump that
extracts its heat and then returns to the ground to absorb more heat from the
earth. Earth loops must be sized properly for each particular geographic area
and individual capacity requirements.
The NorthStar Series heat pumps are designed to operate on either vertical
or horizontal closed loop applications. (Figures 1 & 2) Vertical loops are typically
installed with a well drilling rig up to 200 feet (61 meters) deep or more. Horizontal
systems are typically installed with excavating or trenching equipment approximately
six to eight feet deep, depending on geographic location and length of pipe used.
Lake or Pond Loops – Closed loop systems may also be used in lakes or rivers
to supply a heat source to the heat pump. Typically a loop consisting of
geothermal pipe can be designed and placed in an area not much deeper than
15ft (4.5 meters) with some water currents present. In any lake or pond,
municipal and area codes must be observed in regards to a lake or pond loop.
The use of an environmentally friendly loop fluid like ethanol should be
considered should damage ever occur to the loop. Consult an IGSHPA or CGC
certified installer for proper lake or pond loop design.
Figure 2
Closed Loop
Przeglądanie stron 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 55 56

Komentarze do niniejszej Instrukcji

Brak uwag